DESIGN PROCEDURES — ARCHITECTURAL & STRUCTURAL
PROVISIONS ASSOCIATED WITH & E SERVICES
The list
entitled "Architectural & Structural Provisions Associated with M
& E Services" summarising most of the general
architectural and structural provisions associated with M & E services
which should be taken into consideration at the design and tender documentation
stage. These provisions should be made known to, the Architect, Structural
Engineer and the Quantity Surveyor during the design stage. For some of the
items may have to follow up at a later stage concerning the extent of the items
involved (eg. plinths, louvres, etc.) but
nevertheless, the above list should be issued at the design stage so that the
items concerned will not be left out later.
1.
Structural
loading of the floors and ceiling soffits of plantrooms
and switchrooms should take into account the weight
of the M & E plants as well as the suspended pipes, ducts, etc.
2.
Separator beams
to be provided in between adjacent lift hoistways at
2500mm intervals (the first one commencing at 1500mm from the lift pit).
3.
Hoisting beams
to be provided in the lift machine rooms for positioning/alignment of lift
machines.
4.
Ceiling access
panels to be provided for servicing, maintenance of fan coil units, fire
dampers, equipment in ceiling space, etc.
5.
Access doors to
be provided for inspection of soil waste pipes and other pipes.
6.
Concrete plinths
to be provided for M & E plants.
7.
Concrete kerbs to be provided around all electrical, telephone, data
and ELV riser floor openings.
8.
Cat ladders,
railings, etc to be provided for access to secondary plantrooms, sunken pit, lift pits, RC tanks, etc.
9.
Railings,
lead-in pipes, hardware, concrete trench, draw pits, trap door, gratings,
doors, louvres, etc. to
be provided for the SPPG substation.
10.
External
louvres to be provided for mechanical ventilation system,
lift hoistway smoke relief, standby generators, etc.
11.
Metallic
curtain walls shall be designed and constructed so that all panel to panel
connections are electrically continuous.
12.
M & E signages e.g. "WET RISER", 'SPRINKLER CONTROL
VALVE', "ELECTRICAL RISER", etc. to be provided.
13.
Water meter chamber
and gas valve chamber to be provided.
14.
Builder's works
associated with standby generator such as underground RC enclosure, 600mm high
concrete kerbs for fuel service tank, sand filling of underground RC enclosure,
etc.
15.
Grouting of
lift door jambs/architraves and call button/indicator excess openings.
16.
Forming of
floor/wall openings.
17.
Making good and
sealing of openings after running of services (as for the electrical, telephone
and data risers, the excess openings will be fire stopped by the Electrical
Sub-Contractor).
18.
Water proofing
the floors of wet areas such as AHU rooms, pump rooms, water tank rooms, etc.
19. Dust proofing the floors of transformer rooms, switchrooms,
etc.