CABLE SIZING
1)
The current carrying capacity (ccc) of a cable
is governed by:-
a)
Method of Installation
i)
Cables installed on trays have higher ccc than
those of the same size but enclosed in trunkings or
conduits because the trays afford better heat removal than trunkings/conduits.
E.g. 4 x 70 sq
mm/IC PVC cables in trunking = 171 A
4x 70 sq mm/IC PVC/PVC cables on tray = 223 A
ii)
Cables installed on horizontal trays have higher ccc
than those of the same size but installed on vertical trays because the
horizontal trays afford more surface area for heat removal.
b)
insulation Material
Insulation material which can withstand higher temperatures would allow
the conductor to operate at higher temperature and hence increase the ccc. E.g., PVC insulation can only operate up to 70°C while
XLPE up to 90°C.
c)
Cable Arrangement
i)
Cables which are spaced say one diameter apart have higher ccc than those of same size but installed touching each
other.
ii)
Cables in trefoil formation have lower ccc than
those of same size in flat touching formation.
E.g., 3 x 6 sq
mm/1C MI cables laid flat touching clipped direct = 52 A
3
x 6 sq mm/1C MI cables laid trefoil clipped
direct = 48A
d)
Single Core or Multicore
Single core cables have
higher ccc than multicore cables of the same size.
E.g., 4 x 10 sq mm/1C PVC cables in conduit = 50 A
1 x 10 sq mm/4C PVC cables in conduit 46 A
e)
Grouping
If more than one set of cables are used to increase the ccc, the total ccc will be equal to the sum of the ccc but
reduced by an appropriate grouping factor.
E.g., 4 x 400 sq mm/1C PVC/PVC cables on tray = 679 A
8 x 400 sq mm/1C PVC/PVC cables on tray = 679
x 2 x 0.8 A
= 1086.4 A
f)
Single Phase or 3 Phase
Cables of the same size in single phase
circuit have higher ccc compared with 3 phase circuit
probably because the 3 pahse cables experience higher
mutual heating.
E.g., 2 x 25 sq mm/1C PVC cables in conduit = 101 A
4
x 25 sq mm/1C PVC cables in conduit = 89
A
g)
Ambient Temperature
The ccc of cables decreases as the ambient
temperature increases. The ccc of cables tabulated in CP5 (1988) is based on 30°C. if the ambient temperature is 35°C, a factor of
0.94 has to be applied to the ccc. Refer to Table 901 of CP5 (1988) for other ambient temperature derating factors [See Attachment F].
2)
In spite of several factors affecting
the ccc of cables, we
could generalize the method of installation,
type of cables, cable arrangement, etc. so
as to simplify our cable sizing and selection as follows:
a)
In general, single core cables are to be specified.
b)
All cables (PVC,
XLPE/PVC & FR) will generally be run in conduits or trunkings
for sizes up to and
including 70 sq mm.
c)
Cables of 95 sq mm
and above shall be run on trays. PVC cables (in this instance) shall be of PVC insulated
and PVC sheathed (i.e., PVC/PVC).
d)
Assume all cables within each circuit will
be laid in flat touching formation. For multi-group cables, assume they will be
stacked in tiers.
e)
Assume ambient temperature to be 30°C.
3) With all the above assumptions (which are generally on the conservative
side), the cable sizing against various ratings of MCCBs are tabulated in
Attachment 'A'. The sizing is based on the following:-
a)
For PVC and
PVC/PVC cables, the ccc are based on Columns 4,5 &
9 of Table 9D1 of CP5 (1988) [See Attachment G].
b)
For MI cables, the ccc are based
on Columns 2, 4 & 11 of Table 9J2 of CP5 (1988) with a factor
of 0.9 applied to the tabulated figures to account for the case of bare cables
without PVC sheath [See Attachment I].
c)
For FR cables, the ccc are based on Fujikura
cables at 30°C ambient temperature and 75°C conductor temperature [See Attachment J].
d)
For XLPE cables, the ccc are based on Enamelled
Wire Cables at 30°C ambient temperature and 90°C conductor temperature, flat
touching formation. The grouping factor for 2 groups of cables Is based on 0.8 since it is assumed that the cables will not
be laid in one layer [group factor for one layer Is 0.9 (horizontal) and 0.85
(vertical)] [See Attachment K].
4) The cable sizing summarised
in Attachment A should be taken only as a quick guide in specifying of cable sizes and account should be
taken of the following:‑
a)
Voltage drop (cable sizes may have to be increased if the permissible
volt drop limit Is exceeded).
b)
Any abnormal ambient temperature.
c)
Different methods of running the cables, e.g.,
underground or in trenches, etc.
d)
Use of multicore cables instead of single core
cables.
5) For motor circuits, Clause 552.1L of CP5
(1988) allows the cables to be sized for a current at least equal to the
full-load current rating of the motor. To account for voltage drop and heating
due to frequent starting of certain motors, we should select based on full load
current but one size higher. A tabulation of the cable sizes for various
ratings of motors are given in Attachment B.