DESIGN GUIDELINES & CRITERIA FOR INTERIOR LIGHTING

 
 

 


A.             CALCULATION OF AVERAGE ILLUMINANCE

1.0         Formula:

Average Illuminance, (or Illumination Level) E = 

where   N = No. of Luminaires

1 = No. of Lamps per Luminaire

= Initial Lumen Output (i.e. Luminuous Flux per Lamp in Lumens)

MF = Maintenance Factor

CU = Coefficient of Utilization

L = Length of Room in Meters

W = Width of Room in Meters

2.0         Illumination Level

The illumination level required depends on the usage of the room. The Singapore Standard SS-531 - Lighting of Work Places  (Schedule of Lighting Requirements8) contains a list of recommended illumination levels for various areas.

The designed average illumination levels are as follows:-

Office                    500 lux at desk height

Lobby/Corridor         100 to 150 lux at floor level

Carparks/Driveways: 75 lux at floor level

Car Ramps                     75 and 300 lux at floor level during night and day respectively

3.0         Lumen Output

The initial value of the lumen output of the lamps should be used in the calculations. The initial value refers to the lumen output after 100 hours operation; however, if the lighting design lumens are used (i.e., after 2000 hours operation), the maintenance factor should be adjusted accordingly.

Typical initial values of lumen output of various types of lamps are tabulated in Appendix Al.

4.0         Maintenance Factor

The illumination levels will decrease progressively during use due to:—

(i)    depreciation in lumen output

(ii)  accumulation of dust/dirt on the luminaires and room surface.

Hence the design should make allowance for these factors by initially providing an illuminance which is higher than that required.

As a guide, the following factors could be applied to the calculations:—

Room category

Luminaire and Room Surface Dirt Maintenance  Factor

Lamp—Lumen Maintenance Factor

Total Maintenance Factor

Clean

0.9

0.9

0.8

Average

0.8

0.9

0.7

Dirty

0.7

0.9

0.6

5.0         Coefficient of Utilisation

The coefficient of utilisation (also known as utilisation factor) depends on the following:

a)  Type of luminaire use   - more efficient luminaires have a higher CU.

b) Configuration and size of the room  -   a large room would lead to a higher CU. For the same area, a square room would lead to a higher CU compared with a rectangular room.

c) Surface reflectance of the ceiling, walls and working place of the room. A light coloured surface would reflect more light to the task area.

To determine CU

(a)      First determine the room index, RI =                    L x W             .

          (H—h)(L+W)

Where           H = mounting height of luminaire from floor

H = height of working plane from floor.

(a)      Then estimate or make an assumption on the ceiling/wall/working place reflectance; a typical value would be 70/50/10.

(b)          From the RI and reflectance, read off the CU value from the CU table of the selected luminaire.

(c)           An example of a CU ta5le for Philips FCS229 luminaire is shown below:-

Text Box: 3
3
3
Text Box: 3Text Box: 3 3 3 3 3
a

6.0         Room Cavity Ratio

For certain types of luminaires (particularly for USA made), the CU tables are based on room cavity ratio (RCR) instead of room index.

RCR =                          5 (H-h) (L+W)

         (L x W)

 

RI       =   L x W   .

(H-h)(L+W)

 

Hence RCR =             5   .

RI

Therefore, the RCR could be converted from RI and the CU could be obtained.

7.0         RI for Irregular Shape Rooms

For irregular shape rooms, the RI could be calculated as follows:-

 

8.0         Average Reflectances of Room Surfaces

 

9.0         Lighting Load

After working out the no. of luminaires required, the lighting load should be checked to ensure that it does not exceed the maximum limit stipulated in SS-530 : Code of Practice for Energy Efficiency.

10.0     Spacing of Luminaires

When the total no. of luminaires has been computed, the layout of the luminaires should be determined in conjunction with the ceiling grids and other services (e.g., A/C diffusers, sprinklers, speakers, etc.) while keeping as far as possible to the recommended spacing/mounting height ratio.

The S/H ratio could be found from the catalogues of the luminaire concerned.

 

B.             CALCULATION OF ILLUMINANCE AT A POINT

 

1.0         Formula:

 

2.0         Illuminance at a point, p,

Text Box: 1C)          The above should be repeated for each luminaire, i.e.,

Ep (total) = Epi + Ep2 + Ep3 +  ………….

 

3.0         Luminous Intensity

 

a)                        The luminous intensity could be obtained from the intensity distribution curves (or polar curves or candlepower distribution or luminous intensity diagram) of the selected luminaire. Examples of polar curves are shown in Appendix A.

b)                        The intensity distribution for linear type of luminaires are not symmetrical along the longitudinal & transverse directions; hence two polar curves are given.

c)                            Generally, for incandescent lighting fittings (i.e., downlights, etc.), the polar curves are symmetrical in both directions.

4.0         Example

 

 

5.0         Isolux Diagrams

 

(a)  

Plot the values E vs horizontal distance, a, from the luminaire as shown below:

(b)   Using transparent paper, extend the isolux diagram to cover four quadrants.

(c)   The isolux diagram on transparent paper can now be used to determine the illuminance at a particular point by placing it on the lighting plan layout (drawn to the same scale) such that its centre is at that point, and adding up all the illuminance values contributed by the luminaires.

 

 

 

1.0         Indirect Component at a Point

The contribution by reflected or indirect component of illuminance to the illuminance at a point,

 

2.0         Applications

To determine the maximum spacing to achieve at least 0.5 lux at the floor and without exceeding the uniformity ratio of 40 to 1.


Assume 2 x 18W, hence useful lumen output = 2 x 34 50 x 0.8 = 5520 lumens

 

C.             LIGHT QUALITY

1.0         Light quality involves a combination of 3 main factors:‑

·         Visibility

·         Visual Comfort

·         Luminance Ratios

2.0         Visibility

Visibility is the measure of how well one's eyes can distinguish the contrast between an object and its background. Many direct lighting systems produce light source reflections which can obscure image/background contrasts. These reflections (veiling reflections) appear as shiny images on the surface of paper, desk tops, etc.

Because visibility is no longer solely considered a function of the raw footcandle levels, a means of measuring visibility was developed. This method known as Equivalent Sphere Illumination (ESI) accurately rates a lighting system in terms of light quality, not just quantity. The ESI of a system is the equivalent amount of light which would have to be in a theoretical sphere equal to those of the system in question. So the higher the ESI within a system, the better  visibility. Unit of ESI: Lux or footcandle.

The ESI of a quality lighting system could be higher than the raw illumination level. In fact, ESI levels up to 25% below the IES recommended raw footcandle levels can be used to properly light a given area.

3.0         Visual Comfort

Direct glare from a lighting fixture reduces visual comfort, and since lack of visual comfort results in eyestrain, visual tension and reduced worker concentration, it is essential to design an environment without bright light sources. Such type of glare is also known as discomfort glare and depends primarily on:-

·         Luminance of the light sources

·         Number and apparent size of the light sources

·         General luminance of the environment

·         Position of the sources in the field of view.

The following methods of glare evaluation have been officially adopted by the various countries:

(a)           Visual Comfort Probability (VCP) (Americal Method)

This method is used in the USA and Canada. It is expressed as the percentage of people who, when viewing from a specified location and direction within the system, will find it acceptable in terms of visual comfort. Since the VCP ratings are based on the eyes' reaction to fixture brightness, indirect lighting fixtures which generate no direct fixture brightness, have a theoretical VCP factor of 100. However, from a practical viewpoint, the ceiling brightness generated with an indirect system should not exceed 500 footlamberts for optimum visual comfort.

An installation is considered to be glare—free if the VCP is at least 70%.

(b)          IES Glare Index System (British Method)

Used in Great Britain, Scandinavian countries and South Africa. The method is described in British IES Technical Report 10.

(c)           Luminance Limit System (Australian Method)

The Australian Standard Code for the Artificial Lighting of Buildings gives limits for the average luminance of a luminaire depending on the dimensions of the room and the mounting height of the luminaire.

(d)          The Luminance Curve System

Used in Austria, France, Netherlands, Germany and Italy. For method of calculation, refer to attached example.

3.0          Luminance Ratios

The luminance relationship of various surfaces in the visual field is another important consideration in providing quality light. As the eyes leave the task and look at an area of different luminance, there is a sudden loss in the eye's ability to see contrast details in the new area until the eye can adapt to the new light levels. So in order to see the detail of a visual task accurately, quickly, and with a minimum of eye fatigue, brightness or luminance ratios must be kept within the limits shown below:—

Recommended Ratio                                                                 Area

                3:1                                              Task to immediate surroundings

                5:1                                              Task to general surroundings

              10:1                                              Task to remote surroundings

4.0           Reflected Glare and Veiling Reflections

If light sources are reflected by objects having glossy surfaces, bright patches occur which may obscure the details of the objects. If the patches are so bright that they produce a feeling of discomfort, the effect is called reflected glare. If the effect is only as a reduction of contrasts within the area of the task, it is referred to as veiling reflection.

Although veiling reflections are most noticed on glossy surfaces, they exist to lesser or greater degrees on all surfaces, including matt or dull finishes.

Veiling reflections are a degrading influence because they reduce contrast between task information and background material. Veiling reflections make the task less visible. A 1% loss in task contrast requires an increase in illumination from 7% to 15%.

5.0          Luminance

Luminance is a measure of the brightness of an object or light source. It is defined as the luminous flux per sq m being emitted, transmitted or reflected from a surface.

Mathematically, the brightness of a non—luminous diffusely reflecting surface is equal to the product of the illumination falling on the surface and the reflectance of the surface, i.e.,

Luminance          = Illumination x Reflectance, or

Footlamberts = Footcandles x Reflectance factor.

For self—luminous surface,

Luminance = Transmitted Lumens

Area

D.             SELECTION OF LUMINAIRES

 

1.0         Standardisation

For standardisation of selection of luminaires, we should adopt the following designations and types of luminaires:—

 

2.0         Factors to Consider

The following factors should be taken into consideration in the selection of luminaires:-

a)   Usage of the Room/Area

b)   Whether there is a false ceiling - recessed fittings will generally be used if there is a false ceiling.

c)   Types of false ceiling

-   homogeneous (i.e., without grid or T-bars)

-   semi-concealed grid (only main runners are exposed)

-   exposed grid

d)   Dimensions of ceiling grid, metric or imperial

-   1200 mm x 600 mm

-   1200 mm x 300 mm

-   600 mm x 600 mm

-    4 ft x 2 ft

-   4 ft x I ft

-   2 ft x 2 ft

e)   Feasibility of access for maintenance where the luminaires are mounted.

f)   Glare imposed by the luminaire

g)   Aesthetics of the luminaire

h)   Price of the luminaire

i)   Availability of replacement of the luminaire including all its components.

j)   Type of lamp source (lifetime, colour rendition, efficacy, etc.)

k)   Dimensions of the luminaire (whether the recessed depth clashes with services, etc.)

E.              EMERGENCY LIGHTING

1.0         Code of Practice

The Singapore Standard CP 19: Code of Practice For Emergency EvacuationLighting requires the provision of emergency luminaires and exit signs for residential blocks and all commercial and industrial buildings.

2.0         Residential Apartments and Commercial Buildings

2.1 To provide self-contained emergency luminaires at the following locations:-

a)           Near each door to staircase (Clause 8.1.1 of Fire Precautions).

b)          

Along corridors, lobbies, intersection of corridors, change of direction and at change of floor level spaced as follows:-

2.2          To provide essential power supply from the standby generator to serve the lighting at the following areas:- (To be insert ……………….)