Average Illuminance, (or Illumination Level) E =

where N = No. of Luminaires
1
= No. of Lamps per Luminaire
= Initial
Lumen Output (i.e. Luminuous Flux per Lamp in Lumens)
MF
= Maintenance Factor
CU
= Coefficient of Utilization
L
= Length of Room in Meters
W
= Width of Room in Meters
The illumination
level required depends on the usage of
the room. The Singapore
Standard SS-531 - Lighting of Work Places (Schedule
of Lighting Requirements8) contains a list of recommended illumination
levels for various areas.
The designed average illumination levels are
as follows:-
Office 500 lux at desk height
Lobby/Corridor 100 to 150 lux at floor level
Carparks/Driveways:
75 lux at floor level
Car
Ramps 75 and 300 lux
at floor level during night and day respectively
The initial value of the lumen output of the lamps should be used in the
calculations. The initial value refers to the lumen output after 100 hours
operation; however, if the lighting design lumens are used (i.e., after 2000
hours operation), the maintenance factor should be adjusted accordingly.
Typical initial values of lumen output of
various types of lamps are tabulated in Appendix Al.
The illumination levels will decrease
progressively during use due to:—
Hence the design
should make allowance for these factors by initially providing an illuminance
which is higher than that required.
As a guide, the
following factors could be applied to the calculations:—
|
Room category |
Luminaire and Room Surface
Dirt Maintenance Factor |
Lamp—Lumen Maintenance
Factor |
Total Maintenance Factor |
|
Clean |
0.9 |
0.9 |
0.8 |
|
Average |
0.8 |
0.9 |
0.7 |
|
Dirty |
0.7 |
0.9 |
0.6 |
The coefficient of utilisation (also known as utilisation factor) depends on
the following:
a) Type of luminaire use - more
efficient luminaires have a higher CU.
b)
Configuration and size of
the room - a large room would lead to a higher CU. For
the same area, a square room would lead to a higher CU compared with a
rectangular room.
c)
Surface reflectance of the ceiling, walls and
working place of the room. A light coloured surface would reflect
more light to the task area.
To determine CU
(a)
First determine the room index, RI = L x W
.
(H—h)(L+W)
Where H
= mounting height of luminaire from floor
H
= height of working plane from floor.
(a)
Then estimate or make an
assumption on the ceiling/wall/working place reflectance; a typical value would
be 70/50/10.
(b)
From the RI and reflectance, read off the CU value
from the CU table of the selected luminaire.
(c)
An example of a CU ta5le for Philips FCS229
luminaire is shown below:-


![]()
![]()
![]()
![]()
For certain types of luminaires (particularly
for USA made), the CU tables are based on room cavity ratio (RCR) instead of room index.
RCR = 5 (H-h) (L+W)
(L x W)
RI = L x W .
(H-h)(L+W)
Hence RCR = 5
.
RI
Therefore, the RCR could be converted from RI and the CU could be obtained.
For irregular shape rooms, the RI could be
calculated as follows:-


After working out the no. of luminaires required, the lighting load
should be checked to ensure that it does not exceed the maximum limit
stipulated in SS-530
: Code of Practice for Energy Efficiency.
When the total no. of luminaires has been computed, the layout of the
luminaires should be determined in conjunction with the ceiling grids and other
services (e.g., A/C diffusers, sprinklers, speakers, etc.) while keeping as far
as possible to the recommended spacing/mounting height ratio.
The S/H ratio could be found from the catalogues of the luminaire
concerned.


C) The above
should be repeated for each luminaire, i.e.,
Ep
(total) = Epi + Ep2 + Ep3 + ………….
a)
The luminous intensity could be obtained from the
intensity distribution curves (or polar curves or candlepower distribution or
luminous intensity diagram) of the selected luminaire. Examples of polar curves
are shown in Appendix A.
b)
The intensity distribution for linear type of luminaires are not
symmetrical along the longitudinal & transverse directions; hence two polar
curves are given.

c)
Generally, for incandescent lighting fittings
(i.e., downlights, etc.), the polar curves are symmetrical in both directions.


(a)

Plot the values E vs
horizontal distance, a, from the luminaire as shown below:
(b)
Using transparent paper, extend the isolux diagram to cover four quadrants.
(c)
The isolux diagram on
transparent paper can now be used to determine the illuminance at a particular
point by placing it on the lighting plan layout (drawn to the same scale) such
that its centre is at that point, and adding up all
the illuminance values contributed by the luminaires.

The contribution by reflected or indirect
component of illuminance to the illuminance at a point,


To determine the
maximum spacing to achieve at least 0.5 lux at the floor and without exceeding
the uniformity ratio of 40 to 1.

Assume
2 x 18W, hence useful lumen output = 2 x 34 50 x 0.8 = 5520 lumens
·
Visibility
·
Visual Comfort
·
Luminance Ratios
Visibility is the measure of how well one's
eyes can distinguish the contrast between an object and its background. Many
direct lighting systems produce light source reflections which can obscure
image/background contrasts. These reflections (veiling reflections) appear as
shiny images on the surface of paper, desk tops, etc.
Because visibility is no longer solely considered a
function of the raw footcandle levels, a means of
measuring visibility was developed. This method known as Equivalent Sphere
Illumination (ESI) accurately rates a lighting
system in terms of light quality, not just quantity. The ESI of a system is the equivalent amount of light which would have to be in a
theoretical sphere equal to those of the system in question. So the higher the ESI within a system, the better visibility. Unit of ESI: Lux or footcandle.
The ESI of a quality lighting system could be higher than the
raw illumination level. In fact, ESI levels up to 25%
below the IES recommended raw footcandle levels can
be used to properly light a given area.
Direct glare from a
lighting fixture reduces visual comfort, and since lack of visual comfort
results in eyestrain, visual tension and reduced worker concentration, it is essential
to design an environment without bright light sources. Such type of glare is
also known as discomfort glare and depends primarily on:-
·
Luminance of the light
sources
·
Number and apparent size of the light sources
·
General luminance of the environment
·
Position of the sources in the field of view.
The following
methods of glare evaluation have been officially adopted by the various countries:
(a)
Visual Comfort Probability
(VCP) (Americal Method)
This method is used
in the USA and Canada. It is expressed as the percentage of people who, when
viewing from a specified location and direction within the system, will find it
acceptable in terms of visual comfort. Since the VCP
ratings are based on the eyes' reaction to fixture brightness, indirect lighting
fixtures which generate no direct fixture brightness, have a theoretical VCP factor of 100. However, from a practical viewpoint, the
ceiling brightness generated with an indirect system should not exceed 500 footlamberts for optimum visual comfort.
An installation is considered to be
glare—free if the VCP is at least 70%.
(b)
IES Glare Index System (British Method)
Used in
Great Britain, Scandinavian countries and South Africa. The method is described in British IES
Technical Report 10.
(c)
Luminance Limit System
(Australian Method)
The Australian
Standard Code for the Artificial Lighting of Buildings gives limits for the
average luminance of a luminaire depending on the dimensions of the room and
the mounting height of the luminaire.
(d)
The Luminance Curve System
Used in Austria, France,
Netherlands, Germany and Italy. For method of calculation, refer to attached example.
3.0
Luminance Ratios
The luminance relationship of various
surfaces in the visual field is another important consideration in providing quality
light. As the eyes leave the task and look at an area of different luminance,
there is a sudden loss in the eye's ability to see contrast details in the new
area until the eye can adapt to the new light levels. So in order to see the
detail of a visual task accurately, quickly, and with a minimum of eye fatigue,
brightness or luminance ratios must be kept within the limits shown below:—
Recommended Ratio Area
3:1 Task to immediate
surroundings
5:1 Task to general
surroundings
10:1 Task to remote surroundings
4.0
Reflected Glare and Veiling Reflections
If light sources are reflected by objects
having glossy surfaces, bright patches occur which may obscure the details of
the objects. If the patches are so bright that they produce a feeling of
discomfort, the effect is called reflected glare. If the effect is only
as a reduction of contrasts within the area of the task, it is referred to as veiling
reflection.
Although veiling reflections are most noticed
on glossy surfaces, they exist to lesser or greater degrees on all surfaces,
including matt or dull finishes.
Veiling reflections
are a degrading influence because they reduce contrast between task information
and background material. Veiling reflections make the task less visible. A 1%
loss in task contrast requires an increase in illumination from 7% to 15%.
5.0
Luminance
Luminance is a
measure of the brightness of an object or light source. It is defined as the
luminous flux per sq m being emitted, transmitted or
reflected from a surface.
Mathematically, the
brightness of a non—luminous diffusely reflecting surface is equal to the
product of the illumination falling on the surface and the reflectance of the
surface, i.e.,
Luminance =
Illumination x Reflectance, or
Footlamberts = Footcandles x Reflectance factor.
For
self—luminous surface,
Luminance = Transmitted Lumens
Area
D.
SELECTION OF LUMINAIRES
For standardisation of selection of luminaires, we should adopt
the following designations and types of luminaires:—
The following factors should be taken into consideration in the selection
of luminaires:-
a)
Usage of the Room/Area
b)
Whether there is a false ceiling - recessed fittings will generally be
used if there is a false ceiling.
c)
Types of false ceiling
- homogeneous
(i.e., without grid or T-bars)
- semi-concealed
grid (only main runners are exposed)
- exposed
grid
d)
Dimensions of ceiling grid, metric or imperial
- 1200
mm x 600 mm
- 1200 mm x 300 mm
- 600 mm x 600 mm
- 4 ft x 2 ft
- 4
ft x I ft
- 2
ft x 2 ft
e)
Feasibility of access for maintenance where the luminaires are mounted.
f)
Glare imposed by the luminaire
g)
Aesthetics of the luminaire
h)
Price of the luminaire
i)
Availability of replacement of the luminaire including all its
components.
j)
Type of lamp source (lifetime, colour
rendition, efficacy, etc.)
k)
Dimensions of the luminaire (whether the recessed depth clashes with
services, etc.)
E.
EMERGENCY LIGHTING
The Singapore Standard CP 19: Code of Practice For
Emergency EvacuationLighting requires the provision
of emergency luminaires and exit signs for residential blocks and all
commercial and industrial buildings.
2.1 To provide self-contained emergency luminaires at the following
locations:-
a)
Near each door to staircase (Clause 8.1.1 of Fire Precautions).
b)

Along corridors,
lobbies, intersection of corridors, change of direction and at change of floor
level spaced as follows:-
2.2 To provide essential power supply from the
standby generator to serve the lighting at the following areas:- (To be insert ……………….)