GUIDELINES
FOR CALCULATION OF SHORT CIRCUIT CURRENTS
The purpose of performing short circuit calculations is to predict the prospective short circuit currents (PSCC) due to symmetrical faults occurring at various points in an electrical distribution network.
Having determined the PS CC at various points of application, the associated electrical equipment should then be selected so that they are able to withstand the mechanical and electrical stress produced during a fault.
The main items of concern are normally the switchboards and distribution boards (together with the MCCBs therein), busbar trunkings, etc.
Let I be the rated current
V be the rated voltage
Z be the impedance of the system
Then Z% = I x Z / V x 100% (i.e. the percentage impedance drop)
Z =
Z% x V .
100 x I
Short Circuit
Current, ISC =
V
Z
= V x 100 x I = 100 x I
Z% x V Z%
Short Circuit KVA, KVASC
= ISC
x V = 100 x I
Z%
Example: For a 2000 KVA transformer having 6% impedance,

For percentage impedance for different base, the calculation is as follow:-
For Base A ,
|
ZA% |
= |
IA x Z x 100% |
|
VA |
If it is required to
convert the ZA% to say Base B,
|
ZB% |
= |
IB x Z x 100% |
|
VB |
||
|
ZA% |
= |
IA x VB |
|
ZA% |
IB x VA |
Therefore, ZB% = VA X IB x ZA
VB x IA
If VA = VB, then ZB % = KVAB x ZA %
KVAA
The per unit impedance is
|
Z p.u. = |
Z x I |
|
V |

When a fault occurs, all motor loads connected to the
transformer concerned will continue to run but as generators, contributing to
the fault.
In order to calculate the degree of contribution, the percentage of the motor load to the transformer load should first be determined.
If it is anticipated that the loads from one transformer may be transferred to another transformer, then such loads from both transformers should be considered, of course within the designed capacity of one transformer.

As the source of the fault originates from the SP PowerGrid supply, it is necessary to know the characteristics related to the fault level at the SPPG grid.
In the SPPG Handbook on Application for Electricity Supply, it is indicated that the short circuit MVA for a 22 KV supply is 1000 MVA.


Transformer impedances are usually given in the manufacturers' catalogues as percentage impedance.
Generally, the higher the KVA of the transformer, the higher will be the percentage impedance.

.

Full load loss is determined by short circuit test which delivers full load current at the primary and hence the secondary side.
Incidentally, the voltage applied, in this
instance, is equal to the impedance voltage, i.e., 6.1% of rated voltage.
Note: 6.1% V causes full load current (FLC) to flow

Therefore, total loss = 3450 + 10320 = 13770 W
Transformer Capacity = 0.8 x 1600 = 1280000 watts
It is noted that the losses is typically about 1% or slightly higher .
Formula to calculate R:

The resistances and reactances of busbars and cables can be found in manufacturers' catalogues and the values are usually expressed in m ohms/metre.
If you are working on a base of 400 volts, the impedances of the cables on the HV side should be multiplied by 230'/220002 (if the HV = 22 KV).
In the absence of data from manufacturers, the cable resistance can be derived as follows:

After the prospective short circuit currents have been calculated at the various distribution boards, sub-switchboards and main switchboards, the next step is to ensure that the board as a whole has sufficient rupturing capacity to withstand the fault level.
For main switchboards, they should generally be type tested to withstand up to the specified short circuit MVA for 3 seconds, e.g., 31 MVA, 45 MVA. For a 31 MVA PSCC rated main switchboard, the short circuit withstand current is thus 45 KA and generally all the MCCBs should be rated at 45 KA or more.
For sub-switchboards and distribution boards, it is usually not economical and practical (in particular for DBs) to select all the MCCBs to be at least the same KA rating as the prospective fault level. As such, various recognised methods have been adopted to enable selection of MCCBs of lower KA rating as follows:—
10.1
Cascade Protection
|
|
|
Note that only cascade combinations recommended by manufacturers can be recognised as a means of cascade protection.
Cascade protection is recognised in Clause 4 34.4 of CP5 (1988) which states:-
"A lower breaking capacity is permitted if another protective device having the necessary breaking capacity is installed on the supply side. In that case, the characteristics of the devices shall be coordinated so that the energy let-through of these two devices does not exceed that which can be withstood without damage by the device on the load side and the conductors protected by these devices."
10.2 Back Up Fuses
|
|
·
To ensure that the fuse does not blow often, the rating should be
higher than that of the incoming MCCB. To size the
fuse rating, draw the curves of the fuse, MCCB and
the calculated fault current ·
Look at the “Let Through” current of the selected fuse. ·
All the downstream MCCBs can sized to suit the “Let Through” fault current instead of the PSCC. |
The current limiting effect reduces as the current rating of the fuse increases (generally fuse rating of > 400 A practically no limiting effect).
Ensure that the DB/SB has sufficient space and the fuses are readily accessible.
Eg. A 100A back up fuse will limit a prospective short circuit current of 20 KA to only 7 KA.
For high fault current, can consider to use “Current Limiting” MCCB on either the incoming MCCB or the upstream MCCB.
Refer to the current limiting MCCB’s curves similar to those for fuses.
.


REFERENCES
Table of Resistance (R) and Reactance
(X) Values For Busbars
|
|
Current
Rating (Amp) |
R (milliohm/M) |
X (milliohm/M) |
|
|
225 |
0.0777 |
0.035 |
|
COPPER BUSBAR |
400 |
0.0797 |
0.035 |
|
600 |
0.0830 |
0.035 |
|
|
800 |
0.0877 |
0.035 |
|
|
1000 |
0.0633 |
0.0267 |
|
|
1200 |
0.050 |
0.0217 |
|
|
1350 |
0.0423 |
0.0187 |
|
|
1600 |
0.033 |
0.015 |
|
|
2000 |
0.0243 |
0.0113 |
|
|
2500 |
0.0167 |
0.008 |
|
|
'3000 |
0.0163 |
0.0077 |
|
|
4000 |
0.012 |
0.0057 |
|
|
|
5000 |
0.0087 |
0.0037 |
|
Aluminum Busbar |
225 |
0.1363 |
0.035 |
|
400 |
0.140 |
0.035 |
|
|
600 |
0.1507 |
0.035 |
|
|
800 |
0.0827 |
0.0217 |
|
|
1000 |
0.0723 |
0.0187 |
|
|
1200 |
0.0573 |
0.015 |
|
|
1350 |
0.0413 |
0.0113 |
|
|
1600 |
0.037 |
0.010 |
|
|
2000 |
0.03 |
0.008 |
|
|
2500 |
0.0273 |
0.007 |
|
|
3000 |
0.0213 |
0.0057 |
|
|
4 000 |
0.015 |
0.0037 |
Table of Resistance (R) and
Reactance (X) Values For Copper Cables
|
Cabe |
R (m-iohm/M) |
X (m-ohm/M) |
|
1.5 |
13.3 |
0.118 |
|
2.5 |
7.27 |
0.11 |
|
4 |
4.52 |
0.093 |
|
6 |
3.02 |
0.088 |
|
10 |
1.79 |
0.084 |
|
16 |
1.13 |
0.08 |
|
25 |
0.712 |
0.079 |
|
35 |
0.514 |
0.074 |
|
50 |
0.379 |
0.073 |
|
70 |
0.262 |
0.071 |
|
95 |
0.189 |
0.07 |
|
120 |
0.150 |
0.069 |
|
150 |
0.122 |
0.068 |
|
185 |
0.0972 |
0.068 |
|
240 |
0.0740 |
0.068 |
|
300 |
0.0590 |
0.067 |
|
400 |
0.0461 |
0.067 |
|
500 |
0.0366 |
0.066 |
|
630 |
0.0283 |
0.065 |
|
800 |
0.0221 |
0.064 |
|
1000 |
0.0176 |
0.063 |
Note: Resistance values based on maximum conductor resistance at 20°C single core cable in accordance with Table 2 of SS 50 (1981).
Volt drop resistances are usually based on 70°C and as such, are higher than the 20°C resistance. The latter should be used as a short circuit could occur even when the cable is not loaded.
Table of Resistance (R) and
Reactance (X) Values For Dry Type Cast Resin Transformers
|
Size Code |
Transformer (KVA) |
R (milliohm) |
X (milliohm) |
|
1 |
100 |
28.8 |
91.58 |
|
2 |
125 |
22.0 |
73.58 |
|
3 |
160 |
16.25 |
57.76 |
|
4 |
200 |
12.4 |
46.37 |
|
5 |
250 |
9.22 |
37.28 |
|
6 |
315 |
6.93 |
29.67 |
|
7 |
400 |
5.2 |
23.43 |
|
8 |
500 |
3.97 |
18.79 |
|
9 |
630 |
1.88 |
15.12 |
|
10 |
800 |
1.88 |
11.85 |
|
11 |
1000 |
1.41 |
9.50 |
|
12 |
1250 |
1.07 |
7.61 |
|
13 |
1600 |
0.78 |
5.95 |
|
14 |
2000 |
0.56 |
4.77 |
|
15 |
2500 |
0.46 |
3.81 |
Note: Above figures calculated from "Geofol" transformer catalogues using the 6% impedance voltage