SIZING OF MCCRs FOR MOTORS

 

1)      Full Load Current of Motors

 

a)      Formulae :

 

3-Phase, P =  x V x I x p.f. x eff. (V = 400 volts)

 

P

I = ---------------------------          Amps
 x V x p.f. x eff

 

Single-Phase, P = VxI x p.f. x eff. (V = 230 volts)

 

P

= -------------------- Amps

   V x I x p.f. x eff.

 

where       P             = rated full load output of selected motor in KW

p.f.         = power factor of motor at full load

eff.         = efficiency of motor at full load

 

Note: 1 horsepower (HP) = 0.746 KW

 

b)      Power Factor and Efficiency

 

Generally, the efficiency and power factor increases with the capacity of the motor. The efficiency and power factor also depend on the RPM and percentage of loading on the motor. Typical values of full load p.f. and efficiency for 3 "Crompton Parkinson" motors are given below:-

 

HP

KW

 

p.f.

eff.

0.75

0.55

 

0.65

0.77

1

0.75

0.70

0.77

1.5

1.1

 

0.74

0.77

3

2.2

 

0.79

0.80

5.5

4

 

0.83

0.83

7.5

5.5

 

0.83

0.84

10

7.5

 

0.84

0.86

20

15

 

0.86

0.87

40

30

 

0.86

0.91

75

55

 

0.87

0.92

100

75

 

0.87

9.92

50

110

 

0.92

0.925

200

150

 

0.92

0.93

 

 

 

 

 

 

Note: Above power factor and efficiency based on RPM of approximately 1500 rpm.

 


c) i) Single-Phase Motors

 

We specified motors above 1 HP to be of 31%

 

Average values of p.f. and eff. for 11 motors of 0.5 to 1.0 HP are approximately 0.80 and 0.69 respectively.

 

Hence for single-phase motors of 0.5 to 1.0 HP,

 

kW x 1000

I = --------------------   = 8 xkW

      230 x 0.80 x 0.69

ii) 3-Phase  Motors

Based on values of p.f. and eff. in b) above,

For motors of 0.75 to 1.1 KW,                           l = 2.6 x KW

1.5 to 3 KW,                            1 = 2.4 x KW

3.7 to 5.5 KW,                            = 2.2 x KW

7.5 to 15 KW,                             = 2.0 x KW

22 to 75 KW,                          I = 1.85 x KW

90     W and above,                 I = 1.7 x KW

Note: Ensure that the KW figures given are the rated full load output of the selected motor.

2)      Starters

Usually, the type of starters to be specified should be as follows:-

Up to 5 HP (3.73 kW)                      -  DOL Starter

Above 5 HP to 20 HP (15kW)       - Star-Delta Starter

Above 20 HP                                      - Auto-Transformer Starter.

Variable Speed Drive may be specified for smooth starting as well as limiting the starting current

Exception:         For sewage ejector pumps, NEA stipulated that S/D starters shall be used for all motors of 2.2 KW (3 HP) and above.

 

3)      Starting Current

DOL - Up to 7.5 times FLC.               (note: FLC. = full load current)

1                                 .

S/D - Up to 7.5 x — or 2.5 times FLC.

3

A/T - Up to 7.5 x 0.42 to 0.752 or 1.2 to 4.2 times FLC.

For A/T starters, normally the tappings could not be set too low, otherwise there will be insufficient torque to drive the motor. Hence, for calculation purposes we could assume starting currents of 2 to 3 times FLC.


4)            Selection of MCCB

 

a)   For DOL Starter.

 

DOL starting normally takes about 5 to 10secs. Since most MCCBs will not trip within 10 secs if loaded to 3 times its rated current, the rating of the MCCB for DOL starters could be selected by dividing the starting current by 3.

7.5

Hence, Current rating of MCCB  =          --------      x FLC

3

= 2.5 x FLC.

b) For S/D and AfT Starters

These starting methods normally take about 20 secs. Since most MCCBs will not trip within 20 secs If loaded to 2 times its rated current, the rating of the MCCB could be selected by dividing the starting current by 2.

Hence, current rating of MCCB for Star Delta starters

2.5

= ------- = 1.25 times FLC

2

for Auto-Trans Starters

2              3

= ------- to --— = 1 to 1.5 times FLC.

     2              2

However, to account for inaccuracy of the transformer tappings, residual voltage in the motor during restarting, voltage fluctuation, etc., we should, in general, select an MCCB of rating about 1.5 times the FLC. of the motors for both S/D and A/T starters.

5)              Examples

a)   Single Phase , 1 HP motor :  FLC = 0.75 KW x 8          = 6 Amp

MCCB = 6 x 2.5                            = 15 Amp

 

b)   3-Phase, 3HP motor            :  FLC = 3 x 0.75 x 2.4 = 5.4 Amp

MCCB = 5.4 x 2.5                        = 13.5 Amp say 15 Amp
(Type of Starter = DOL)

 

Note: For 3-Phase  motors less than 3 HP, select MCCB of 15A even though 10A may be adequate.

 

c)   3-Phase 15 'HP motor  : FLC = 15 x 0.75 x 2 = 22.5Amp

MCCB = 22.5 x 1.5                      = 33.75 Amp say 40 Amp
(Type of Starter = S/D)

6.             Summary

 

Type of Starters

MCCB Rating

DOL Starters

FLC. x 2.5

Star Delta Starters

FLC x 1.5

Auto Transformer Starters

FLC x 1.5


A selection chart showing the MCCB ratings for various KW rating of motors against various types of starters can be found in Attachment C.

A formula for determining the current rating of incoming MCCB/Fuse of Switchboards serving more than one motor Is shown In Attachment D.