VOLTAGE DROP CALCULATION

1.                    Clause 522.8 of CP5 (1988) stipulates that the maximum permissible voltage drop from the origin of the installation to the most remote part should not exceed 2.5%, i.e., 10V for 3 phase (400 V) and 5.75 V for single phase (230 V).

 

2.                    The voltage drop data given In the tables are usually based on the full ccc which result in the maximum conductor operating temperature (e.g., 70°C for PVC cables). When the cable is not loaded up to the full ccc, the voltage drop/amp/metre is lower since the conductor temperature is also lower than the maximum operating temperature (hence lower Impedance).           

 

3.                    In general, the figures 'Z' (e.g., Table 9D1 of CP5 (1988), Attachment H) are used for calculation of voltage drop.

 

4.                    Grouping of cables would generally result in lower voltage drop.

e.g., 600 A Submains, 100 m

Use 4 x 400 sq mm/1C PVC/PVC on tray (679 A)

V.D.         =             0.24 x 600 x 100                   =             14.4 V

Use 8 x 185 sq mm/1C PVC/PVC on tray (2 x 424 x 0.8 = 678 A)

V.D.         =             0.31 x 300 x 100                   =            9.3 V

 

5.                    Cables laid in trefoil have very low voltage drop. This laying method can be specified to overcome excessive voltage drop.

e.g., 600 A Submains, 100 m

Use        4 x 400 sq mm/1C PVC/PVC laid flat on tray (679 A)

V.D.         =             0.24 x 600 x 100 = 14.4 V

Use        4 x 400 sq mm/1C PVC/PVC laid in trefoil on tray (679 A)

V.D.         =             0.175 x 600 x 100 = 10.5 V

 

6.                    For more accurate assessment of the volt drop, the following formula on Pg 155 of CP5 (1988) can be used:-

Volt drop in mV/A/M     =   cos f x [tabulated (mV/A/M)rj + sin f x [tabulated (mV/A/M)x]

Volt drop figures obtained in this manner is usually lower than the tabulated figures using 'Z'.

E.g., mV/A/M for 4 x 400 sq mm/1C                    =  0.24 (Z)

If p.f. = 0.85, cos f= 0.85               sin f' = 0.527

Hence, mV/A/M              =             0.85 x 0.11 + 0.527 x 0.21

0.935    .1107                          =             0.204

 

 

7.               The designed current to be used in the voltage drop calculation should preferably be based on the current rating of the circuit breaker to allow for any possible future additional loads that may be imposed on the circuit. However, in some cases, this may lead to rather excessive voltage drops and unnecessary oversizing of cables to overcome the voltage drop. The designed current to be used in the calculation should then be reviewed on a case by case basis to take into account cases such as those circuit breakers which are oversized to afford discrimination, or for standardization, etc.

 

8.               For 3 phase circuit, the distance is taken from the source to the point (where volt drop calculation is desired) without considering the return direction since it is assumed that the 3 phase currents are balanced and relatively little neutral current. For single phase circuit, the return line (neutral) distance must be considered. However, the volt drop tabulations given in CP5 has taken this into account and hence, the distance is again taken from source to point for single phase circuits.