VOLTAGE DROP
CALCULATION
1.
Clause 522.8 of CP5 (1988) stipulates that the maximum permissible
voltage drop from the origin of the installation to the most remote part should
not exceed 2.5%, i.e., 10V for 3 phase (400 V) and 5.75 V for single
phase (230 V).
2.
The voltage drop data given In the tables are
usually based on the full ccc which result in the maximum conductor operating
temperature (e.g., 70°C for PVC cables). When the cable is not loaded up to the
full ccc, the voltage drop/amp/metre
is lower since the conductor temperature is also lower than the maximum
operating temperature (hence lower Impedance).
3.
In general, the figures 'Z' (e.g., Table 9D1 of CP5 (1988), Attachment H)
are used for calculation of voltage drop.
4.
Grouping of cables would generally result in lower voltage drop.
e.g., 600 A Submains, 100 m
Use 4 x 400 sq mm/1C PVC/PVC on tray (679 A)
V.D. = 0.24
x 600 x 100 = 14.4 V
Use 8 x 185 sq mm/1C PVC/PVC on tray (2 x 424 x 0.8 = 678 A)
V.D. = 0.31 x 300 x 100 = 9.3 V
5.
Cables laid in
trefoil have very low voltage drop. This laying method can be specified to overcome
excessive voltage drop.
e.g., 600 A Submains, 100 m
Use 4 x
400 sq mm/1C PVC/PVC laid flat on tray (679 A)
V.D. = 0.24 x 600 x 100 = 14.4 V
Use 4 x 400 sq mm/1C PVC/PVC laid in trefoil on tray (679 A)
V.D. = 0.175
x 600 x 100 = 10.5 V
6.
For more
accurate assessment of the volt drop, the following formula on Pg 155 of CP5 (1988) can be used:-
Volt drop in mV/A/M = cos f x [tabulated (mV/A/M)rj + sin f x [tabulated (mV/A/M)x]
Volt drop figures obtained in this manner is usually lower than the
tabulated figures using 'Z'.
E.g., mV/A/M for 4 x 400 sq
mm/1C = 0.24 (Z)
If p.f. = 0.85, cos f= 0.85 sin
f' = 0.527
Hence, mV/A/M = 0.85 x 0.11 + 0.527 x 0.21
0.935
.1107 = 0.204
7.
The designed
current to be used in the voltage drop calculation should preferably be based
on the current rating of the circuit breaker to allow for any possible future
additional loads that may be imposed on the circuit. However, in some cases,
this may lead to rather excessive voltage drops and unnecessary oversizing of
cables to overcome the voltage drop. The designed current to be used in the
calculation should then be reviewed on a case by case basis to take into
account cases such as those circuit breakers which are oversized to afford
discrimination, or for standardization, etc.
8.
For 3 phase
circuit, the distance is taken from the source to the point (where volt drop
calculation is desired) without considering the return direction since it is
assumed that the 3 phase currents are balanced and relatively little neutral
current. For single phase circuit, the return line (neutral) distance must be
considered. However, the volt drop tabulations given in CP5 has taken this into
account and hence, the distance is again taken from source to point for single
phase circuits.