Generator Set Shop Drawing Checklist

Rounded Rectangle: Download PDF Copy
 

 

 


Item

Description

Check

Remarks


1

Confirm brand, rating (prime), voltage, frequency, engine, alternator model are correct and based on tender/ contract specifications:

 

 

 

 

Tender Offer

Actual Submission

 

 

 

a.       Diesel Engine Brand

 

 

 

 

 

b.      Alternator Brand

 

 

 

 

 

c.       Engine Power (kW)

 

 

 

 

 

d.      Alternator Rating (kVA)

 

 

 

 

 

e.      Voltage/Frequency

 

 

 

 

2

Enclosure Noise level

 

 

a.       Specified: Max ____  dBA at 1 m. (usually 75 dBA)

b.      Offered : ___________________

 

 

3

Parts of genset are correctly labelled on drawings

 

 

 

a.       Diesel Engine

 

 

b.      Alternator

 

 

c.       Radiator

 

 

 

d.      Silencer

 

 

e.      Control Panel

 

 

f.        Fuel Tank with capacity indicated

 

 

4

Output breaker rating is correct

Specified :  ________________ Amp (TPN / 4-Pole)

Offered :   _________________ Amp (TPN / 4-Pole)

 

 

5

Confirm size and height of canopy set can fit into space allocated. Minimum maintenance space of 0.9m all around canopy should be provided. Check that doors can be fully opened without hindrance.

 

 

6

Check orientation and location of genset with respect to site and site constraints

 

 

7

Provision of light fitting (minimum IP65 type) inside canopy c/w switch near access door.

 

 

8

1000 litres sub-base fuel tank capacity correct and sufficient for 6 hours continuous operation. Details of fuel top-up and drainage shown

 

 

9

Fuel top up location to be near entrance for easier fuel top up

 

 

10

Provision of battery rack and provision of calculations to confirm sufficient capacity for cranking 6 times

 

 

11

Provision of lifting eyes for hoisting purposes

 

 

12

Provision of calculation for confirmation of quantity and type of vibration isolators. Vibration isolators shall also be provided with neoprene pads.

 

 

13

To include comment for contractor to submit the calculation and catalogue to Acoustic Consultant for review.

 

 

14

Colour of canopy to be advised by Architect. Painting schedule to be provided.

 

 

15

Provision of earthing boss to connect to lightning protection

 

 

16

Provision of built-in ladder to access top of canopy set for maintenance

 

 

17

Provision of viewing window should not turn yellow as it ages. (e.g. non-UV stabilised plastics, acrylics, etc.).

 

 

18

Provision of ironmongeries (i.e. hinges, handles, locks, etc.) to be of non-rusting type (e.g. stainless steel)

 

 

19

Door locks shall be openable from inside to avoid man trap situation during maintenance

 

 

20

Rubber stopper on every door to prevent banging

 

 

21

Cable entry details shown and c/w weather shield and fibre cable gland plate. Cables shall be housed inside hot dipped galvanised cable tray/ladder c/w galvanised cover and cables are not directly exposed to weather

 

 

22

Drainage for rainwater provided for cases whereby canopy set air intake and/or air discharge are facing upwards

 

 

23

Sufficient distance between air intake and blank wall (minimum 1m) and/or between air discharge and blank wall to allow proper air intake and discharge

 

 

24

Cap for exhaust pipe whereby exhaust pipe outlet is facing upwards to prevent rainwater during non-usage. Sufficient space shall be catered to allow for cap opening

 

 

25

Provision of BMS interfacing points for monitoring purpose.  (Refer to Schedule 2 for BMS Point Schedule)