Residential Unit Shop Drawing Checklist
![]()
|
Item |
Description |
Check |
Remarks |
|
1 |
Types of luminaires, switch socket outlets, telephone
points, CCTV cameras, speakers and other ancillary services |
|
|
|
2 |
Check to ensure latest architectural layout is used |
|
|
|
3 |
Reflected ceiling plan layout and the latest services
layout coordinated by main contractor |
|
|
|
4 |
Fixing details of luminaries, speakers, CCTV cameras and
other ancillary services |
|
|
|
5 |
Fixing heights of: |
|
|
|
a)
wall
luminaries, box speakers - 2.5m AFFL (above finished floor level) in
staircases |
|
|
|
|
b)
CCTV |
|
|
|
|
i.
Dome Type -
at ceiling level |
|
|
|
|
ii.
-Non-dome
type - mounted on wall - 0.2m below ceiling height |
|
|
|
|
iii.
- Outdoor
type - IP65 enclosure - typically 3.5m AFFL |
|
|
|
|
c)
Switches -
1.4m to bottom of switch unless otherwise specified by Architect |
|
|
|
|
d)
Switched
socket outlets |
|
|
|
|
i.
- 1.4m AFFL
to bottom of SSO (plantrooms) |
|
|
|
|
ii.
- 0.3m AFFL
to bottom of SSO (Other areas where asethetically
concerned) |
|
|
|
|
e)
Distribution
Boards - Top of DB to be not more than 1.8m AFFL |
|
|
|
|
f)
Intercom
panel - 1m AFFL |
|
|
|
|
6 |
Luminaires to be wired using alternate looping arrangement |
|
|
|
7 |
Not more than 10 luminaires looped in one circuit |
|
|
|
8 |
Battery pack or emergency source lighting to achieve lux
level in accordance to SS563 |
|
|
|
9 |
Provision of emergency circuit for non-battery pack light fittings
for extended hours of power outage (after battery pack backup hours) |
|
|
|
10 |
Conduit/ trunking/ tray/ duct routing layout - to indicate
bottom of tray |
|
|
|
11 |
Conduit/ trunking space factor |
|
|
|
a)
Conduit 40% |
|
|
|
|
b)
Trunking 45% |
|
|
|
|
c)
Duct - 35% |
|
|
|
|
12 |
SSOs, DBs exposed and accessable
to public shall be lockable |
|
|
|
13 |
Isolators used shall be 4P or DP |
|
|
|
14 |
All electrical fittings exposed to weather shall be
minimum IP65 rated |
|
|