Item |
Description |
Check |
Remarks |
|
|||
|
1 |
Check short circuit rating of board and type test
certificate. |
|
|
|
|||
|
2 |
Check busbar size. Cross sectional area of busbar x
1.55A/mm2 shall be equal or larger than the required ampere rating |
|
|
|
|||
|
3 |
Check all amperes rating, no. of poles, short circuit
rating of all outgoing breakers against project requirement. |
|
|
|
|||
|
4 |
Outgoing breakers shall be 1.5 time smaller than the
incoming breaker to ensure proper coordination |
|
|
|
|||
|
5 |
Check connection from main busbar to outgoing breaker.
Size of busbar/ cable shall be sized based on ampere frame (AF) of the MCCB |
|
|
|
|||
|
6 |
For SP PowerGrid main incomer, check that O/C, E/F relays
complies to Appendix 17.2 of SPPG Handbook |
|
|
|
|||
|
7 |
Check all cables and CPC sizes against voltage drop |
|
|
|
|||
|
8 |
Check all technical particulars of: |
|
|
|
|||
|
a)
Class, rating
and ratio of current transformers |
|
|
|
||||
|
b)
Indicating
lights. All indicating lights shall be of LED type |
|
|
|
||||
|
c)
Meters.
Ensure correct range is used |
|
|
|
||||
|
d)
Fuses &
links |
|
|
|
||||
|
e)
Selector
switch |
|
|
|
||||
|
f)
Panel
heaters/ thermostats |
|
|
|
||||
|
9 |
All RCCBs shall be 4P or DP. Check sensitivity of RCCB |
|
|
|
|||
|
10 |
There are no AT/AF rating for MCBs |
|
|
|
|||
|
11 |
ZCTs shall be provided for ELRs. Check setting range of
ELRs |
|
|
|
|||
|
12 |
Shunt trips shall be provided for ELRs, O/C relays, E/F
relays |
|
|
|
|||
|
13 |
For power monitoring systems, all power meters shall be
provided with interfacing points for BMS connection |
|
|
|
|||
|