Single Line Diagram Drawing Checklist

Rounded Rectangle: Download PDF Copy
 

 

 

 


Item

Description

Check

Remarks

 

1

Check short circuit rating of board and type test certificate.

 

 

 

2

Check busbar size. Cross sectional area of busbar x 1.55A/mm2 shall be equal or larger than the required ampere rating

 

 

 

3

Check all amperes rating, no. of poles, short circuit rating of all outgoing breakers against project requirement.

 

 

 

4

Outgoing breakers shall be 1.5 time smaller than the incoming breaker to ensure proper coordination

 

 

 

5

Check connection from main busbar to outgoing breaker. Size of busbar/ cable shall be sized based on ampere frame (AF) of the MCCB

 

 

 

6

For SP PowerGrid main incomer, check that O/C, E/F relays complies to Appendix 17.2 of SPPG Handbook

 

 

 

7

Check all cables and CPC sizes against voltage drop

 

 

 

8

Check all technical particulars of:

 

 

 

a)       Class, rating and ratio of current transformers

 

 

 

b)      Indicating lights. All indicating lights shall be of LED type

 

 

 

c)       Meters. Ensure correct range is used

 

 

 

d)      Fuses & links

 

 

 

e)       Selector switch

 

 

 

f)       Panel heaters/ thermostats

 

 

 

9

All RCCBs shall be 4P or DP. Check sensitivity of RCCB

 

 

 

10

There are no AT/AF rating for MCBs

 

 

 

11

ZCTs shall be provided for ELRs. Check setting range of ELRs

 

 

 

12

Shunt trips shall be provided for ELRs, O/C relays, E/F relays

 

 

 

13

For power monitoring systems, all power meters shall be provided with interfacing points for BMS connection

 

 

 

 

Checked by:

 

 

File to : _________/EC